Catalogue documentation
Parameters
Accessories
Approval marks
| Rated operating voltage | 690 V |
| Rated operating current | 250 A |
| Utilization category (switching mode) / 400 V a.c. | AC-23B |
| Utilization category (switching mode) / 690 V a.c. | AC-22B |
| Thermal current with fuse-link | 250 A |
| Thermal current with disconnecting link ZP1 | 400 A |
| Rated conditional short-circuit current (RMS) 400 V a.c. / 250 A | 120 kA |
| Rated conditional short-circuit current (RMS) 500 V a.c. / 250 A | 120 kA |
| Rated impulse withstand voltage | 8 kV |
| Rated insulation voltage | 1000 V a.c. |
| Max. power losses of the fuse-link | 32 W |
| Power losses without fuse-link / In | 16 W |
| Degree of protection from front side, built-in device, cover opened | IP20 |
| Degree of protection from front side, built-in device, cover closed | IP20 |
| Remote signalling of fuse state | |
| Remote signalling of cover position | |
| Connecting space cover | |
| Free place cover | |
| Free place cover clips |
Catalogues
Declaration of conformity
Certificates
Manuals
-
Basic catalogue - 1260-Z01/10 (1,18 MB)
-
Declaration of conformity (1) (34,5 kB)
-
Declaration of conformity (2) (55,25 kB)
-
UA UA1.003.0136346-08
(1,42 MB)
-
GOST POCC CZ.AR80.B04888
(1,19 MB)
-
UA UA1.0030017692-07 (3,1 MB)
-
ESČ (CZ) 1110517 (290,63
kB)
-
ESČ (EN) 1110517 (243,73
kB)
-
Cover for parallel outlet -
VP-FD123 (98,46 kB)
-
Switch-disconnector superstructure -
NL-FD123/31/L. (1,86 MB)
-
Remote signalling of fuse state -
NK-FD123 (200,67 kB)
-
Cable outlet earthing cover -
VZ-FD123 (92,89 kB)
com
english
czech
russian
german
polish
slovak