FH2 Fuse switch-disconnectors VARIUS size 2 up to 400 A

Parameters

Rated operating voltage 690 V
Rated operating current 400 A
Utilization category (switching mode) / 500 V a.c. / three-pole design AC-23B
Utilization category (switching mode) / 400 V a.c. / single-pole design AC-23B
Utilization category (switching mode) / 690 V a.c. AC-22B
Utilization category (switching mode) / 440 V d.c. / two-pole connection DC-21B
Utilization category (switching mode) / 440 V d.c. / 250 A single-pole connection DC-21B
Thermal current with fuse-link 400 A
Thermal current with disconnecting link ZP2 520 A
Rated conditional short-circuit current (RMS) 400 V a.c. 120 kA
Rated conditional short-circuit current (RMS) 550 V a.c. 50 kA
Rated conditional short-circuit current (RMS) 690 V a.c. 25 kA
Rated pulse withstand voltage 12 kV / FH2-.A/., 8 kV / FH2-.S/., 12 kV / FH2-3L/.
Rated short-time withstand current 15 kA
Rated short-circuit making capacity / 400 V a.c. 30 kA
Rated insulation voltage 1000 V a.c.
Max. power losses of the fuse-link 34 W
Power losses without fuse-link / In 23 W
Degree of protection from front side, built-in device, cover opened IP20
Degree of protection from front side, built-in device, cover closed IP30

Accessories

Locking insert
Connecting sets
Adapter for busbar system (60 mm)
Remote signalling of fuse state
Remote signalling of cover position
Light indication of fuse state
Assembly kit (2-pole or 4-pole)
Connecting space cover
Barrier against accident contact
Front shield
Spare parts
/uploads/oez/files/ow/small_1293-web_CZ_SK_EN_DE_RU_HU_PL_UA.jpg

Approval marks

CE ESČ
 
 
Web portal supplier - QCM, s.r.o.