Calendar of actions

october 2019
Mo Tu We Th Fr Sa Su
  1 2 3 4 5 6
7 8 9 10 11 12 13
14 15 16 17 18 19 20
21 22 23 24 25 26 27
28 29 30 31      

MMR-U3, MMR-X3 Voltage monitoring relays

Technical support

weekdays: 9:00-15:00 (CET)

Parameters
Accessories
Certification marks
Arrangement of contacts 001
Rated operating voltage AC AC 250 V
Rated operating current AC-1 / AC 250 V 8 A
Rated operating voltage AC (measuring circuit) AC 230/400 V
Rated frequency 50 Hz
Adjustable delay 0 s ÷ 10 s
Adjustable overvoltage level 225 ÷ 265 V
Adjustable undervoltage level 180 ÷ 220 V
Adjustable value of asymmetry 5 ÷ 20 %
Input power max. 1,5 VA
Degree of protection IP20
Conductor rigid Cu 0,2 ÷ 2,5 mm2
Ambient temperature min. -20 °C
Ambient temperature max. 55 °C
EN 60255-1
IEC 60255-1