qr_code

OLE Residual current circuit breakers with overcurrent protection (6 kA)

Catalogue documentation
Parameters
Accessories
Approval marks
Rated operating voltage AC 230 V a.c.
Tripping characteristic B, C
Rated current 6 ÷ 16 A
Rated residual current 30 mA
Rated short-circuit breaking capacity / 230 V a.c. 6 kA
Rated residual making and breaking capacity 6 kA
Surge resistance 1 kA
Rated frequency 50 ÷ 60 Hz
Degree of protection IP20
Type AC
Number of poles 2
Conductor rigid max. 35 mm2
Conductor flexible max. 25 mm2
Ambient temperature min. -5 °C
Ambient temperature max. 40 °C
EN 61009