Categories
OEZ (https://www.oez.com/)

3VA1140-6EF42-0AA0

Moulded case circuit breaker

«
3VA1140-6EF42-0AA0
Product description:
3VA11, In 40 A, Icu 70 kA / 415 V, overcurrent release TM240 (ATAM), Ir 28 ÷ 40 A, Ii (5 ÷ 10)x In, without N-pole protection, 4-pole, front connection
Order Code: 3VA1140-6EF42-0AA0
EAN: 4042948809136
Unit of measure pcs
Send a question to the product

Electrical parameters

Rated current40 A
Min. reduced rated current28 A
Max. reduced rated current40 A
Rated operating voltageAC 690, DC 600 V
Rated operating voltage AC690 V
Rated operating voltage DC600 V
Rated short-circuit ultimate breaking capacity / 415 V70 kA
Rated short-circuit service breaking capacity / 415 V70 kA
Rated frequency50/60 Hz
Setting of instantaneous short-circuit release5;6;7;8;9;10x In
Min. release current of independent instantaneous (short-circuit) release200 A
Max. release current of independent instantaneous (short-circuit) release400 A
Power losses / 1 pole3,6 W
Electrical endurance8000 cycles
Protection from front side of the deviceIP40

Physical parameters

Degree of protectionIP40
Number of poles4
Control element typelever

Mechanical parameters

Mechanical endurance20000 cycles

Dimensions

Width (netto)101,6 mm
Height (netto)130 mm
Depth (netto)70 mm
Weight (netto)1,14 kg
Basic package1 pcs
Collated package- pcs

Working conditions

Ambient temperature min.-25 °C
Ambient temperature max.70 °C

Customs data

Customs Tariff85362010
Country of originCZ
ALN
ECCNEAR99

Database data

PCK5375