Categories
OEZ (https://www.oez.com/)

3VA2612-6KQ42-0AA0

Moulded case circuit breaker

«
3VA2612-6KQ42-0AA0
Product description:
3VA26, In 1250 A, Icu 85 kA / 415 V, overcurrent release ETU860 (LSIG), Ir 500 ÷ 1250 A, Isd (0,6 ÷ 10)x In, Ii (1,5 ÷ 10)x In, Ig (0,2 ÷ 1)x In, tg 0,05/0,8 s, 4-pole, front connection
Order Code: 3VA2612-6KQ42-0AA0
EAN: 4042949435563
Unit of measure pcs
Send a question to the product

Electrical parameters

Rated current1250 A
Min. reduced rated current500 A
Max. reduced rated current1250 A
Rated operating voltage690 V
Rated operating voltage AC690 V
Rated short-circuit ultimate breaking capacity / 415 V110 kA
Rated short-circuit service breaking capacity / 415 V85 kA
Rated frequency50/60 Hz
Setting of instantaneous short-circuit release1,5 ÷ 10x In
Max. release current of independent instantaneous (short-circuit) release10 A
Power losses / 1 pole172 W
Electrical endurance4600 cycles
Protection from front side of the deviceIP40

Physical parameters

Degree of protectionIP40
Number of poles4
Control element typelever

Mechanical parameters

Mechanical endurance10000 cycles

Dimensions

Width (netto)280 mm
Height (netto)320 mm
Depth (netto)120 mm
Weight (netto)25,004 kg
Basic package1 pcs
Collated package- pcs

Working conditions

Ambient temperature min.-25 °C
Ambient temperature max.70 °C

Customs data

Customs Tariff85362090
Country of originCZ
ALN
ECCNEAR99

Database data

PCK5374